Digester level…an interesting problem for Sherlock Boyes…

February 2, 2006 by Walt Boyes

“Daniel M.” wrote to the Automation List at Control.com:
“…we have a waste water treatment plant, and some anaerobic digestor (height 10 m, diameter 13 m). We need to measure level AND INTERFACE in these digestor. Ex zone due to biogas presence. If someone already faced this problem, I would appreciate any comments regarding the apropriate sensor or sensors (I personally think is not possible).”
Here’s what I wrote back:
What you need depends on what you want to measure. Is there foam in the
digester? Do you need sludge blanket interface or liquid/foam interface?
Foam/liquid interface can be measured by guided wave radar (also sometimes
called TDR, time domain reflectrometry), and sometimes by RF admittance
(Drexelbrook, Princo, E+H, and hordes of others).
If you need to measure the sludge blanket in an anaerobic digester, you need
to understand that nothing works really well, even differential pressure
or hydrostatic level.
The reason that nothing works really well is that there is not a sharp, well
defined interface. There is always a “rag layer” which goofs up (that’s the
correct technical term, my wife’s orthopedic surgeon assured me of this) the
reading on radar and RF admittance. You can’t use ultrasonic, even uplooking
ultrasonic, for the same reason.
The thing that I’ve seen work the best is a float that has a custom specific
gravity that is calculated to be approximately (and I use the word
advisedly) the specific gravity of the interface. This can get interesting
if the sludge blanket is almost the same specific gravity as the liquid,
say, 1.02 for the supernatant liquid and 1.1 for the sludge (this can often
happen with organic sludges). Check with one of the good old time float
gauge manufacturers, like Magnetrol, or Krohne.
If you can pull the digester down, you can also try an armored sight gauge,
with optical alarms. But this requires modifying the vessel, and your codes
may make this ugly.
Good luck!

Filed Under: Walt Boyes' Blog

Primary Sidebar


Contact Us Using the Form Below or by Phone at:

  • +1.845.623.1830 (NY)
  • +1.630.639.7090 (WA)
  • +55 (21) 3958.1283 (Brasil)

Subscribe to David W Spitzer’s E-Zine and the Industrial Automation INSIDER

  • This field is for validation purposes and should be left unchanged.

Spitzer and Boyes is a proud member of the Measurement, Control and Automation Association

Follow Us on Social Media

  • LinkedIn
  • Twitter
  • YouTube

Copyright © 2023 · Magazine Pro on Genesis Framework · WordPress · Log in