One of the gases was fed from high pressure gas cylinders, while the other gas was generated in a process unit located approximately 100 meters from the flowmeters. Both flowmeters had sufficient straight run and were installed properly. There were pressure and temperature measurements downstream and upstream of the orifice plate respectively. Flow controllers were used to control the gas flows, and I seem to recall that a multiplier was used to ratio the flows.
Observation of the operation and its recordings revealed that the controlled flow rates of both gases were both controlling at set point, but the process gas flow was less steady than the cylinder gas flow. Both gas temperatures were steady. The pressure of the cylinder gas was steady and at its design pressure. However, the pressure of the gas from the other process unit would vary somewhat near its design pressure and occasionally drop off and recover a few minutes later.
As in many applications, the problem lies in more than one location. First and foremost, these flow measurement systems were not compensated for pressure and temperature variations.
The pressure of the gas from the cylinders should be compensated because even though it could easily be controlled, the pressure gauge used to control its pressure could be in error (or be read incorrectly) and cause significant flow error. The temperature of the gas varied with ambient conditions, so flow errors of a few percent were likely.
The most ominous problem was that of the process gas where the pressure at the flowmeter could vary between 60 to 120 percent of its design pressure and cause significant flow measurement errors. Even when steady, the operating pressure introduced errors because the pressure was only close to its design condition. Temperature variations were less dramatic than the cylinder gas, but could still produce measurement error. Pressure and temperature compensating this gas flow would mitigate the problem and likely eliminate the symptoms.
Pressure and temperature instruments for most flowmeters locate these measurements upstream and downstream of the flowmeter respectively. Note that the designer of this installation located the pressure transmitter downstream on the downstream tap of the orifice plate and the temperature transmitter upstream of the orifice plate. This did not cause problems with this particular installation (but it could with other installations) because orifice calculations were available for the downstream pressure tap location. The temperature transmitter location did not cause a problem because it was installed far enough upstream to not distort the velocity profile in the flowmeter and the temperature difference between the upstream and downstream locations was small.
It is apparent that the person(s) who designed this installation likely did not consider the need for pressure and temperature compensation, and if they did, they did not understand where the transmitters are commonly located. Recognizing that a temperature variation of 3ºC will alter the volume of a gas by approximately 1 percent at near atmospheric conditions, temperature compensation should be considered in virtually all gas applications. Similarly, relatively small pressure variations can cause significant volume changes, so pressure compensation should be considered in virtually all gas applications.
Even if it is decided not to pressure and/or temperature compensate the flowmeter, properly locate and install taps for a pressure and temperature transmitters. They are relatively inexpensive… and you never know when you will need them.
This article originally appeared in Flow Control magazine.